메틀러톨레도 수처리용 전도도 센서
Thornton 243E223, Conductivity Sensor, 0.1 constant, 316LSS 1.5 inch Tri Clamp Fitting - 58031223
- Global Part #: 58 031 223
- US & Canada Part # 243E223
Sensor Selection Criteria Conductivity or resistivity
range – resistivity (Mohm-cm) = 1/conductivity (µS/cm)
Mounting type – Insertion, retractable or submersion
Pipe connection type and size
Suspended solids – four-electrode sensors have flat surfaces which are less likely to accumulate solids
Chemical compatibility, including cleaning and disinfection processes. Rely on process experience or consult
Thornton for unusual process composition. Monel® is recommended for exposure to hydrofluoric acid.
Cell Constant Accuracy ± 1% except ± 5% system accuracy for 4-E and 240-401 sensors (sensor & transmitter calibrated as a matched-pair system at start up)
Cell Constant Repeatability ± 0.25% except ± 2% for 4-E sensors
Temperature Sensor Pt1000 RTD, IEC 60751, Class A
Temperature Accuracy ± 0.1 °C at 25 °C, except 4-E sensors Cable Jacket Material/Temp. rating PVC, 80 °C; except 0.1 constant sanitary & 0.4 constant–PTFE, 200 °C
Maximum Sensor Distance 200 ft (60 m) except 50 ft (15 m) for 244-series Finish (Sanitary 0.1cm-1 Sensors) Ra 8 microinches (0.2 micrometers), 316L SS is electropolished
Insulator Material PEEK (0.1, 0.4 and 0.01 constant sensors)